Overview

HP Modular Cooling System G2

   
 

At a Glance
  • Supports cooling two HP 42U racks at a time at 17.5kW per side or 35kW in a single rack
  • 35kW of cooling capacity, up from 30kW
  • Six hot swappable high airflow fans
  • High air flow heat exchanger with bi-directional air distribution
  • CTO capability of up to 2000 Lbs dynamic load for both the standard MCS G2 rack as well as the MCS G2 Expansion rack
  • Expand MCS G2 to support a second rack with MCS G2 Expansion rack
  • Automatic door opening system for both racks ships standard with every MCS G2. The automatic door opening mechanism is not CTO capable and therefore ships in the accessories box and is to be installed onsite
  • 42U rack height (2 meters) and 1.5 racks wide to maintain datacenter tiling configuration.
  • Environmental Monitor with SNMP integration to Systems Insight Manager (SIM)
  • Power Input Redundancy for dual power source
  • Condensate Evacuation system to prevent condensation from entering air stream
  • Site Preparation Guide available at:
    http://h20000.www2.hp.com/bizsupport/TechSupport/DocumentIndex.jsp?contentType=SupportManual&lang=en
    &cc=us&docIndexId=64179&taskId=101&prodTypeId=3447589&prodSeriesId=3657806
contents
 Overview      Models      Standard Features      Related Options      Technical Specifications line.gif (50 bytes)

Models

Site Preparation  
HP Modular Cooling System G2 Hook up Kit
AF089A
HP MCS G2 Site Preparation Service
NOTE: Use Per Event Support and Consulting Service
http://h20219.www2.hp.com/services/cache/11077-0-0-225-121.aspx.
N/A
NOTE: The Modular Cooling System Water Hook-up kit can be ordered ahead of the MCS G2 for site preparation purposes. The kit contains set of 1.0 inch diameter, Couplings and Parallel-to-Tapered adapter included to address regional differences.  
Modular Cooling System G2 (MCS G2)
HP Modular Cooling System G2 Rack
AF025A
HP 10642 G2 Rack Rear Extension Kit
NOTE: The Rack Rear Extension kit is required when racking the HP c7000 Enclosure in conjunction with an HP Monitored PDU
AF036A
HP Modular Cooling System G2 10642 G2 Expansion Rack
AF026A
HP Install Modular Cooling System Service
NOTE: Install MCS G2 per the product user installation manual. All MCS G2 units ship with shock pallet for CTO.
UE005E
NOTE: Install MCS G2 per the product user installation manual. All MCS G2 units ship with shock pallet for CTO.
NOTE: The purchase of HP Modular Cooling System G2 (P/N AF025A) includes 10642 G2 rack and cooling unit attached.  
NOTE: A loaded MCS G2 rack should only be moved by professional movers.
contents
 Overview      Models      Standard Features      Related Options      Technical Specifications line.gif (50 bytes)

Standard Features

Product Description

HP Modular Cooling System G2 rack is designed for high density server and blade deployments. It re-circulates and cools the hot server exhaust air through the heat exchanger residing in the MCS G2 unit. The air is then expelled in front of the enclosed rack at a much lower temperature providing sufficient cool air for a load of 35kW of servers or blades, or two racks at 17.5kW each.

The MCS G2 unit contains six fans and a heat exchanger deployed along the full height of the rack to ensure that all the equipment installed receives sufficient chilled air. All fans are swappable while the unit is online, providing great servicing flexibility. Redundant power is ensured through a failover power switch that can be connected to two power sources. The environmental monitor controls the air temperature to the servers and adjusts automatically to meet the pre-established air temperature goal. The environmental monitor interacts with HP SIM (Systems Insight Manager) via SNMP traps.

The Water Hookup kit is made available as a separate kit to prepare the water hookup ahead of the arrival of the MCS G2.

A Site Preparation Guide is available for download at:
http://h20000.www2.hp.com/bizsupport/TechSupport/DocumentIndex.jsp?contentType=
SupportManual&lang=en&cc=us&docIndexId=64179&taskId=101&prodTypeId=3447589&prod
SeriesId=3657806
.

This guide provides details on how to prepare the datacenter for the successful deployment of the MCS G2. It may be advisable to contact HP Professional Services for a Site Datacenter Thermal Quick Assessment Service, reference HB691A1 and HB691AE. Visit http://www.hp.com/hps/support for additional information.
The MCS G2 unit mounted next to a HP 10000 G2 Series rack is designed to occupy 1.5 tiles in the datacenter maintaining tile count for cable routing and access to the plenum.

The MCS G2 and the MCS G2 Expansion Rack are CTO capable with a dynamic load capacity of 2000 Lbs each. For HP CTO services go to: http://h18004.www1.hp.com/products/servers/platforms/rackandpower.html

NOTE: A loaded MCS G2 unit should only be moved by professional movers.

NOTE: We support 3000lbs of static IT Equipment on leveling feet.
Caution: Static loading limits cannot be achieved if the rack is

  1. Not on its leveling feet and
  2. Rolled or pushed from its position.

Not responsible for floor damages where the rack resides. Your floor weight capacity may not support the full static load capacity. Check with your floor provider before loading.


HP 10000 G2 Series Rack

All HP rack-mountable products are designed to fit our industry-standard 19-inch wide racks. Racks and rack-mountable components are typically described using "U" measurements. One "U" is 1.75" (44.45 mm) high.

The MCS G2 ships attached to a specially adapted 42U 10000 Series G2 rack 600mm wide (10642). This sturdy, industrial-strength rack series offers the following features:

  • Universal - Accommodates all HP server platforms (ProLiant, BladeSystem, Integrity, HP 9000, Alpha, Storage) in addition to select third party equipment.
    NOTE: MCS G2 does not support rx7xxx, rp7xxx, rp84xx, rx86xx servers, 10U and other 17U servers.
  • Design - The doors on the HP 10000 G2 Series rack bayed to the MCS G2 unit are fitted with carbonite insert mounted inside the front door and solid split rear doors to prevent air from escaping to the environment and to reduce the noise level.
  • Load Capacity - The MCS G2 and the MCS G2 Expansion rack will accommodate up to 2000 lb. of equipment each in a static or dynamic environment. A static environment is one where the rack is positioned into place and the leveling feet are extended prior to equipment being installed. A dynamic environment is one where the rack is shipped on a shock pallet with equipment installed or rolling racks with equipment installed to new locations within the data center.
  • Unique Frame and Rail Design - Enables fast assembly, easy mounting and outstanding structural integrity. Equipment installation effort is dramatically reduced because the vertical mounting system was specifically designed to minimize the time required to install HP products, and can be used with many other non-HP products as well. U markings on the front and sides of rails make it easy to align parts when installing equipment. Cut outs in the rails also allow for cabling between racks.
  • Security Provisions - Front and rear doors are lockable, which provides the necessary level of security to prevent unauthorized entry. Side panels are also lockable* allowing for your entire rack row to be secure

HP MCS G2 Key Features
  • Cooling Capacity of up to 35kW - MCS G2 has been designed to support a full load of blade servers in a single rack or 17.5kW per rack when deployed as a rack solution. The MCS G2 unit will provide cool air distributed along the full height of the MCS G2 rack.
  • Power Input Redundancy - Automatically detects power failure and switches to alternate source.
  • Environmental Control and Safety - The MCS G2 features full environmental control of the cooled air temperature being placed in front of the servers. The heat exchanger unit features safety quick disconnect valves that prevent accidental chilled water leakage during service. A water leak detector ships standard with the MCS G2. Alarms can be sent via SNMP traps to Systems Insight Manager (SIM).
  • Hot-swappable components - Fans can be replaced while the unit is operating allowing for great flexibility in servicing the MCS G2.

Industry Standard Support

All rack products are 19 inch RETMA standard and will support select third-party equipment. For additional rack information, please refer to the HP 10000 G2 Series rack QuickSpecs at: http://h18004.www1.hp.com/products/servers/proliantstorage/racks/10000g2series.html


HP Care Packs

HP Modular Cooling System: One year warranty, parts only (1-0-0)
HP 10642 G2 Series Rack: Three year warranty, parts only (3-0-0)
NOTE: Certain restrictions and exclusions apply. Consult the HP Customer Support Center for details.

Care Pack services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical.
A full range of HP Care Pack hardware and software services are available including:

  • Installation and start up
  • Education courses
  • Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24 hours, 7 days call window with options including 4-hour response or 6-hour Call To Repair
  • Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials and VMware-base d IT solutions helping to deliver high level of application availability. Response times range from 30 mins for critical problems to 2 hours.
  • System Management, Performance Services and Mission Critical Support Solution

NOTE: For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at: http://www.hp.com/hps/carepack
NOTE: For more complete information on HP Services offerings, customers and resellers, please visit us at: http://www.hp.com/hps
NOTE: Additional information regarding worldwide limited warranty and technical support is available at: http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html
NOTE: For additional information on Server Services, Rack and Power Options, please visit: http://h20219.www2.hp.com/services/cache/111072-0-0-225-121.html
NOTE: The information contained herein is subject to change without notice and is provided "as is" without warranty of any kind.

NOTE: The warranties for HP products and services are set forth in the express limited warranty statements accompanying such products and services.
NOTE: Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.

contents
 Overview      Models      Standard Features      Related Options      Technical Specifications line.gif (50 bytes)

Related Options

NOTE: This is a list of supported options. Some may be discontinued.  
Rack Light Kit HP Light Kit for 10000 Series Rack
NOTE: This neon light kit is mounted inside the rack and used to provide light to the rear section of the rack.
361589-B21

Grounding Kit HP 10000 G2 Series Rack Grounding Kit
AF074A

HP Cable Management Kits Cable Management D Rings
168233-B21
HP Rack Cable Management Velcro Clips
NOTE: 50 pack.
379820-B21

Universal 1U Filler Panels HP 1U 10-pack Carbon Universal Filler Panel
AF070A
HP 1U 100-pack Carbon Universal Filler Panel
AF071A

HP Locking Drawer HP 2U Universal Locking Drawer
361591-B21

Rack Shelves 10000 Rack 1U Monitor Utility Shelf
253449-B21
100kg Sliding Shelf
234672-B21

Cable Trays Kits HP 600 Wide Rack Top Cable Tray
NOTE: 8-Pack.
383982-B21
HP Rack Top Cable Mgmt Transfer Tray
383984-B21

Rear Extension Kits HP 42U Rack 200mm Rear Extension Kit
NOTE: The 10642 G2 extension kit is required when using HP monitored PDU's.
AF036A

HP Care Packs Hardware Services On-site Service
HP 3 year Next business day Modular Cooling System Hardware Support
UE001E
HP 3 year 4 hour 13x5 Modular Cooling System Hardware Support
UE002E
HP 3 year 4 hour 24x7 Modular Cooling System Hardware Support
UE003E
HP 3 year 6 hour 24x7 Call to Repair Modular Cooling System Hardware Support
UE004E
Installation Services  
HP Install Modular Cooling System Service
NOTE: Install MCS G2 per the product user installation manual, BTO MCS G2 units only, no CTO units.
UE005E
contents
 Overview      Models      Standard Features      Related Options      Technical Specifications line.gif (50 bytes)

Technical Specifications

MCS G2 Specifications
Dimensions Height in U 42U
Maximum Height 78.9 in (2004 mm)
Maximum Width 35.8 in (909 mm)
Maximum Depth 51 in (1,270 mm)
Shipping Height (on skid) 88.5 in (2248 mm)
Shipping Width (on skid) 48 in (1220 mm)
Shipping Depth (on skid) 70 in (1778 mm)
Ramp length 103 in (2616 mm)
Total length required for offloading MCS G2 20.25 ft (6.17 m)
Weight Net (including rack) 434 kg (957 1bs)
Shipping 1370 lbs (621.4 kg)
Load Static 3000 lbs. (1364 kg)
Dynamic (CTO) weight allowed 2000 lbs (908 kg)
Color Graphite Metallic Doors
Carbon Frame
Hot Swap Components Heat exchangers No
Fans Yes
Cooling Cooling agent Primary or auxiliary chilled water supply
Condensate evacuation tube Yes
Air temperature regulation Yes
Heat exchangers 1
Fans 6
Rack Front door Transparent polycarbonate insert behind mesh
Rack Rear doors (split) Solid, no mesh
Chilled water connections Rear
MCS G2 mounting location Left hand side
Side panels included Yes
Max Cooling capacity 35kW
Air Temperature to servers Settable, suggested at 68-77 ° F ( 20-25° C)
Air Flow to servers 2400 CFM Max
Recommended Chilled Water inlet temperature 45.0 ° F ( 7.00 ° C) 7° to 15° C
Maximum Chilled Water Flow Rate 15.8 US gallons per minute (60 liters per minute)
Chilled Water Pressure Drop 17 psi (1.2 bar) at 60 liters per minute
Water connections 1.00 in (25.4 mm)
Coupling type 1.00 in NPT or BSPP (G type) supplied in Main Hose Kit AF089A
Flexible hose length (not-installed) 3.5 m(11.5 ft)
Pipe thread Parallel (parallel-to-tapered adapter included)
Power Input Nominal Input Voltage 208-240 VAC + - 10%
Frequency range (min-max) 50/60 Hz
Input Power 1900 Watts Max
Single phase Yes
Rated line current 15 A per line cord
Max inrush current 54 A peak for 20 ms per line cord
Dropout carry through time at min voltage 20 ms
Circuit breaker rating 20A per line cord
Power factor correction >0.98 at all loads
Ground leakage current (mA) <3.0 (mA) per line cord
Input Connections USA, Japan NEMA L6-20P
Input Connections International IEC309 (16 Amps)
Power Cords 2 (for redundancy)
Power input redundancy Yes, with auto failover switch
Environment Room temperature requirements 41.0 ° F (5° C) Min to 95.0 ° F (35.00 ° C) Max
Humidity Range Allowable 20%-80%
Recommended 40%-55%
Environmental Monitoring Air temperature to servers control Yes
Water-In temperature monitor Yes
Communications & Management Control panel Multi-function LCD status and control console
SIM 5.0 Integration Yes, via SNMP traps
RJ 45 Plug 1
Certifications Regulatory Approvals UL Listing 484,
CUL Canadian std. 22.2 No.236
EN61000-3-2
EN61000-3-3 Flicker
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
CB report to IEC 60950-1
TÜV / GS EN 60335-1 (according to 60335-2-40)
Warranty Standard MCS G2 Warranty 1-0-0
Standard Rack Warranty 3-0-0

MCS G2 Expansion Rack Specifications
Dimensions Height in U 42U
Maximum Height 78.9 in (2004 mm)
Maximum Width 24 in (600 mm)
Maximum Depth 51 in (1,270 mm)
Shipping Height (on skid) 88.5 in (2248 mm)
Shipping Width (on skid) 48 in (1220 mm)
Shipping Depth (on skid) 70 in (1778 mm)
Ramp length 103 in (2616 mm)
Total length required for offloading MCS G2 20.25 ft (6.17 m)
Weight Net 253 lbs (115 kg)
Shipping 284 lbs (129 kg)
Load Static 3000 lbs (1364 kg)
Dynamic (CTO) weight allowed 2000 lbs (908 kg)
Color Graphite Metallic Doors
Carbon Frame
Warranty MCS G2 Expansion Rack 3-0-0

Environment-friendly Products and Approach

End-of-life Management and Recycling Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to http://www.hp.com/go/green. To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.


© Copyright 2011 Hewlett-Packard Development Company, L.P.

The information contained herein is subject to change without notice.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.


   DA-12919 7 - Version 7 - June 20, 2011